| TYPE |
Portable transformer winding resistance meter |
| PHYSICAL SPECIFICATIONS |
16.8”W x 12.6”H x 10.6”D (42.6 cm x 32.0 cm x 27 cm); Weight: 27 lbs (12.2 kg) |
| INPUT POWER |
100 – 120 Vac or 200-240 Vac (factory pre-set), 50/60 Hz |
| RESISTANCE READING RANGE |
1 micro-ohm – 2,000 ohms |
| ACCURACY |
1 – 19,999 micro-ohms: ±0.5% reading, ±1 count; 20 – 999 milli-ohms: ±1% reading, ±1 count; 1 – 2,000 ohms: ±1.5% reading, ±1 count |
| TEST VOLTAGE |
36 Vdc max |
| TEST CURRENT RANGE |
Auto range, 10 Amperes max |
| DISPLAY |
Back-lit LCD Screen (16 characters by 2 lines); viewable in bright sunlight and low-light levels |
| CONTROL |
Single “turn-and-push” knob |
| COMPUTER INTERFACE |
RS-232C port (19,200 baud) used for factory calibration and diagnostics |
| SAFETY |
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards |
| ENVIRONMENT |
Operating: -10˚C to 50˚ C (15˚F to +122˚ F); Storage: -30˚ C to 70˚ C (-22˚F to +158˚ F) |
| CABLES |
Three 50-foot test cables, ground cable, power cord and cable bag |
| OPTIONS |
Transportation case |
| WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F). Last updated on February 16, 2009 |