| TYPE |
Portable, automatic, CVT, VT, PT turns-ratio tester |
| PHYSICAL SPECIFICATIONS |
19.5" x 12" x 17" D (49.5 cm x 30.5 cm x 43.2 cm) |
| INPUT POWER |
100 – 120 Vac or 220 – 240 Vac (selectable), 50/60 Hz |
| MEASUREMENT METHOD |
ANSI/IEEE C57.12.90 |
| RATIO-MEASURING RANGE |
75 - 10,000 (5 digit resolution) |
| TURNS-RATIO ACCURACY |
75 - 4,999: ±0.25%, 5,000 – 9,999: ±0.35%, 10,000 - 15,000: ±0.5% |
| PHASE ANGLE READING |
0-360 degrees, ±0.2 degree accuracy |
| POLARITY |
In-Phase or Out-of-Phase indication |
| TEST VOLTAGE |
7440Vac @ 50ma |
| DISPLAY |
Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels |
| COMPUTER INTERFACE |
RS-232C |
| PC SOFTWARE |
Windows XP/Vista/7 Transformer Analysis Software (included with purchase) |
| INTERNAL TEST RECORD STORAGE |
128 test records. Each record contains 33 readings. |
| EXTERNAL TEST RECORD STORAGE |
Up to 999 test records on external USB Flash drive. |
| SAFETY |
Designed to meet IEC 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 Standards |
| ENVIRONMENT |
Operating: -10ºC to 50ºC (15ºF to +122ºF) Storage: (-30ºC to 70ºC (-22ºF to +158ºF) |
| HUMIDITY (MAX) |
90% RH @ 40˚ C (104˚ F) non-condensing |
| ALTITUDE (MAX) |
2000m (6562 ft) to full safety specifications |
| CABLES |
One 50 ft. H cable, one 15 ft. X cable, one power cable, one safety ground cable |
| WARRANTY |
One year on parts and labor |
| Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F). |